China Suppliers BV Single-Core Non-Sheathed Cable Factory | IEC 60227-01, 450/750V, Rigid Conductor
Construction
(1) Conductors
Number of conductors: 1.
The conductors comply with the requirements of IEC 60228:
- class 1 for solid conductors;
- class 2 for stranded conductors.
(2) Insulation
The insulation is polyvinyl chloride compound of type PVC/C applied around the conductor.
Technical Performance
Maximum conductor temperature in normal use: 70°C.
The use of the cable type 60227 IEC 01 comply with IEC 62440, which provides guidance on the safe use of electric cables with a rated voltage not exceeding 450/750 V.
Parameter Table
| 1 | 2 | 3 | 4 | 5 | 6 |
|
Nominal cross- sectional area of conductor mm² |
Class of Conductor IEC 60228 |
Thickness of insulation Specified value mm |
Mean overall diameter |
Minimum insulation resistance at 70°C MΩ · km |
|
|
Lower limit mm |
Upper limit mm |
||||
| 1.5 | 1 | 0.7 | 2.6 | 3.2 | 0.011 |
| 1.5 | 2 | 0.7 | 2.7 | 3.3 | 0.010 |
| 2.5 | 1 | 0.8 | 3.2 | 3.9 | 0.010 |
| 2.5 | 2 | 0.8 | 3.3 | 4 | 0.009 |
| 4 | 1 | 0.8 | 3.6 | 4.4 | 0.00805 |
| 4 | 2 | 0.8 | 3.8 | 4.6 | 0.00707 |
| 6 | 1 | 0.8 | 4.1 | 5 | 0.00700 |
| 6 | 2 | 0.8 | 4.3 | 5.2 | 0.00600 |
| 10 | 1 | 1 | 5.3 | 6.4 | 0.00700 |
| 10 | 2 | 1 | 5.6 | 6.7 | 0.00605 |
| 16 | 2 | 1 | 6.4 | 7.8 | 0.00500 |
| 25 | 2 | 1.2 | 8.1 | 9.7 | 0.00500 |
| 35 | 2 | 1.2 | 9 | 10.9 | 0.00403 |
| 50 | 2 | 1.4 | 10.6 | 12.8 | 0.00403 |
| 70 | 2 | 1.4 | 12.1 | 14.6 | 0.00305 |
| 95 | 2 | 1.6 | 14.1 | 17.1 | 0.00305 |
| 120 | 2 | 1.6 | 15.6 | 18.8 | 0.00302 |
| 150 | 2 | 1.8 | 17 | 21 | 0.00302 |
| 185 | 2 | 2 | 19 | 23 | 0.00302 |
| 240 | 2 | 2.2 | 22 | 26.6 | 0.00302 |
| 300 | 2 | 2.4 | 24.5 | 29.6 | 0.00300 |
| 400 | 2 | 2.6 | 27.5 | 33.2 | 0.00208 |
Advantages
(1) Consistent Product Quality
We achieve outstanding product quality through meticulous selection of premium materials and implementation of cutting-edge production technologies. Our quality assurance system operates through four critical checkpoints: initial material evaluation, production line monitoring, intermediate product testing, and final quality certification. To ensure complete accountability, we maintain comprehensive production records and retain representative samples from each batch, enabling full product history tracking.
(2) Industry-Leading Delivery Speed
Our extensive inventory system keeps substantial stock levels for all product lines, allowing us to immediately respond to emergency orders. The combination of our pre-processed component reserves and adaptable manufacturing system enables us to effectively handle various urgent customer needs while maintaining high standards.
(3) Tailored Customization Services
For special order requirements, we've developed an optimized project coordination process. Every customized order benefits from exclusive support provided by our integrated specialist team, which includes product developers, account managers, manufacturing experts, and support staff working collaboratively. This approach guarantees that each client receives solutions that precisely match their technical specifications and business objectives.
Frequently Asked Questions (FAQ)
The conductors are designed with a single-conductor structure and comply with the requirements of the IEC 60228 standard, including class 1 for solid conductors and class 2 for stranded conductors.
The cable is insulated using a high-quality polyvinyl chloride (PVC) compound of type PVC/C, which is applied directly around the conductor.
Under normal operating conditions, the maximum conductor temperature is rated at 70°C.
The 60227 IEC 01 cable complies with IEC 62440 guidelines, which cover safety requirements for electric cables with a rated voltage not exceeding 450/750 V.
We employ a rigorous four-checkpoint quality assurance system: initial material evaluation, production line monitoring, intermediate product testing, and final quality certification. Full traceability is maintained through batch records and retained samples.
Yes, we offer tailored customization services supported by an integrated specialist team, including developers, account managers, and manufacturing experts, to meet your exact technical specifications.